2711P-T10C4D1 is an Allen-Bradley PanelView Plus 1000 touch terminal from Rockwell Automation. It was designed to run FactoryTalk View Machine Edition (ME) applications as a local machine-level operator interface. The catalog number identifies a 10.4-inch color touch HMI with built-in Ethernet and RS-232 communications and DC input power.
Official lifecycle answer: Rockwell Automation lists 2711P-T10C4D1 as Discontinued, with a discontinued date of December 31, 2012.
Technical specifications
Specification
Official Rockwell Automation data
Manufacturer / brand
Rockwell Automation / Allen-Bradley
Catalog number
2711P-T10C4D1
Product family
PanelView Plus 1000
Operator input
Analog-resistive touch screen
Display
10.4-inch color active-matrix TFT LCD
Display area
211 × 158 mm (8.3 × 6.2 in.)
Resolution / color
640 × 480 pixels; 18-bit color
Luminance
300 cd/m² (nits)
Built-in communications
10/100Base-T Ethernet and RS-232; USB support
Application flash
64 MB, as stated in Rockwell's catalog cross-reference for this exact model
Application platform
FactoryTalk View Machine Edition applications
DC input
24 V DC nominal; 18…32 V DC operating range
DC power consumption
70 W maximum (2.9 A at 24 V DC); 39 W typical (1.6 A at 24 V DC)
Approximate dimensions
248 × 329 × 55 mm (9.77 × 12.97 × 2.18 in.), H × W × D, base-configured unit without communication module
Panel cutout
224 × 305 mm (8.8 × 12.00 in.), H × W, for a 1000 touch terminal
Approximate weight
2.6 kg (5.7 lb), base-configured 1000 touch unit
Operating temperature
0…55 °C (32…131 °F)
Non-operating temperature
-20…+70 °C (-13…+158 °F)
Relative humidity
5…95%, noncondensing
Enclosure ratings
NEMA Type 12, 13, 4X (indoor use only); IEC IP54 and IP65
Installation values above come from Rockwell Automation's 2711P-IN001 installation instructions for PanelView Plus 700…1500 terminals. Always confirm the terminal series and product label before installation.
What is the 2711P-T10C4D1 used for?
Rockwell Automation positions FactoryTalk View ME as a dedicated HMI platform for machine-level operator-interface devices. Accordingly, the 2711P-T10C4D1 is used on installed machines where operators need a local graphical interface for monitoring and control. The exact screens, controller connections, alarms, trends, security, and language functions depend on the FactoryTalk View ME application loaded by the machine builder or system integrator.
Its built-in Ethernet and RS-232 interfaces make the terminal relevant to legacy control systems that were engineered around these communication paths. Rockwell's user manual is intended for personnel who install, operate, or troubleshoot PanelView Plus terminals and states that users must understand the FactoryTalk View ME application running on the device.
Application areas
Rockwell Automation positions PanelView Plus terminals and FactoryTalk View Machine Edition as machine-level operator-interface solutions that monitor, control, and graphically display application status. For this legacy terminal, the most relevant application areas are:
⚙
Machine operation
Local start/stop, mode selection, setpoint entry, and machine-status visualization as defined by the FactoryTalk View ME application.
🖥
Monitoring and response
Operator access to graphical status, alarms, trends, security, and language functions configured by the machine builder.
🔌
Legacy control panels
Installed systems engineered around built-in 10/100 Ethernet, RS-232, USB, 24 V DC power, and the legacy PanelView Plus 1000 cutout.
↻
Maintenance and migration
Application backup, terminal replacement, and engineered migration to newer PanelView platforms after compatibility validation.
Application note: Exact functions depend on the FactoryTalk View ME project and controller architecture. Industry-specific suitability must be verified from the installed machine design, terminal series, and product label.
Is 2711P-T10C4D1 discontinued, and what replaces it?
Yes. Rockwell Automation discontinued 2711P-T10C4D1 on December 31, 2012. Rockwell's official PanelView Plus-to-PanelView Plus 6 catalog conversion guide maps the base terminal 2711P-T10C4D1 to 2711P-T10C4D8.
That conversion model, 2711P-T10C4D8, was itself discontinued on December 30, 2021. Rockwell now identifies 2711P-T10C22D9P as its engineering replacement. The 2711P-T10C22D9P is currently listed as Active and is a PanelView Plus 7 Performance terminal with a 10-inch SVGA TFT touch display, 800 × 600 resolution, Ethernet DLR, 24 V DC input, and Windows 10 IoT Core.
Migration stage
Catalog number
Rockwell lifecycle / role
Original terminal
2711P-T10C4D1
Discontinued 2012-12-31
Official PanelView Plus 6 conversion
2711P-T10C4D8
Discontinued 2021-12-30
Current engineering replacement
2711P-T10C22D9P
Active PanelView Plus 7 Performance
Migration caution: “Engineering replacement” does not mean automatic drop-in interchangeability. The D1, D8, and D9P platforms differ in operating system, memory, resolution, network architecture, and software generation. Review the panel cutout and mounting, FactoryTalk View ME source/runtime file, firmware, controller shortcuts, communications, and application testing before changing hardware.
2711P-T10C4D1 FAQ
What is Allen-Bradley 2711P-T10C4D1?
It is a PanelView Plus 1000 color touch HMI with a 10.4-inch 640 × 480 TFT display, Ethernet and RS-232 communications, USB support, 24 V DC input, and FactoryTalk View ME application support.
Is 2711P-T10C4D1 discontinued?
Yes. Rockwell Automation lists it as discontinued effective December 31, 2012.
What is the official replacement for 2711P-T10C4D1?
Rockwell's conversion guide maps it first to 2711P-T10C4D8. Because the D8 model is also discontinued, Rockwell's product catalog now identifies 2711P-T10C22D9P as the active engineering replacement in this migration path. Engineering validation is required.
Can I install 2711P-T10C22D9P without changing the application?
Do not assume a direct swap. The replacement uses a newer platform, operating system, resolution, and Ethernet architecture. Review and test the FactoryTalk View ME application, communications, mounting, and firmware before commissioning.
What software is used with 2711P-T10C4D1?
PanelView Plus terminals run FactoryTalk View Machine Edition applications. Rockwell's platform comparison lists legacy PanelView Plus 700…1500 application support for FactoryTalk View ME versions 3.20…5.10; the exact usable version depends on the terminal firmware and application.
Does 2711P-T10C4D1 have Ethernet?
Yes. Rockwell identifies built-in 10/100 Ethernet and RS-232 communication for this base terminal configuration, together with USB support.
What are the panel cutout and power requirements?
Rockwell's installation instructions give a 224 × 305 mm (8.8 × 12.00 in.) cutout for a 1000 touch terminal. DC input is 24 V nominal with an 18…32 V DC range.
Based on over 5000 reviews
Description:2711P-T7C21D8S PanelView Plus 7 Standard Terminal
Product condition: New
Packing condition:Factory Packing
100% insured shipping: A guarantee for your purchases
PLC Autocontroller DELIVER PARTS TO WORLD.
Based on over 5000 reviews
Description:6AV2124-0MC01-0AX0 Comfort Touch Panel
Product condition: New
Packing condition:Factory Packing
100% insured shipping: A guarantee for your purchases
PLC Autocontroller DELIVER PARTS TO WORLD.
Based on over 5000 reviews
Description:Allen-Bradley 2711PC-T6C20D8 is a compact, 6-inch color PanelView Plus 6 terminal that delivers rock-solid performance and instant visibility to your machines in even the tightest control-panel spaces.
Product condition: New
Packing condition:Factory Packing
100% insured shipping: A guarantee for your purchases
PLC Autocontroller DELIVER PARTS TO WORLD.
Based on over 5000 reviews
Description:Allen-Bradley 1784-PKTS — ControlNet communication interface module for high-speed PLC networking and reliable industrial data exchange in automation systems.
Product condition: New
Packing condition:Factory Packing
100% insured shipping: A guarantee for your purchases
PLC Autocontroller DELIVER PARTS TO WORLD.
Based on over 5000 reviews
Description:Allen-Bradley 1784-PCMK — ControlNet PCMCIA communication interface card for PLC programming, monitoring, and reliable industrial network connectivity.
Product condition: New
Packing condition:Factory Packing
100% insured shipping: A guarantee for your purchases
PLC Autocontroller DELIVER PARTS TO WORLD.
Based on over 5000 reviews
Description:Allen-Bradley 1784-PCMC1 — ControlNet PCMCIA communication interface card for reliable PLC communication, programming, and industrial automation network access.
Product condition: New
Packing condition:Factory Packing
100% insured shipping: A guarantee for your purchases
PLC Autocontroller DELIVER PARTS TO WORLD.
Based on over 5000 reviews
Description:Allen-Bradley 1784-PCIS — ControlNet PC interface communication card for reliable PLC networking, data exchange, and industrial automation system integration.
Product condition: New
Packing condition:Factory Packing
100% insured shipping: A guarantee for your purchases
PLC Autocontroller DELIVER PARTS TO WORLD.
Based on over 5000 reviews
Description:Allen-Bradley 1784-KTXD — DH+/DH-485 communication interface card for reliable PLC networking, remote I/O access, and industrial automation system communication.
Product condition: New
Packing condition:Factory Packing
100% insured shipping: A guarantee for your purchases
PLC Autocontroller DELIVER PARTS TO WORLD.