INPUT, FILTERING & SENSOR POWER
B&R ID code0x22A8
Module diagnosticsRun/error via LED status indicator and software
Bus power consumption0.14 W
Internal I/O power consumption0.59 W
Hardware input filter≤100 µs
Software input filterDefault 1 ms; configurable from 0 to 25 ms in 0.2 ms increments
Low switching threshold<5 VDC
High switching threshold>15 VDC
Nominal input voltage24 VDC
Input characteristicsType 1 per EN 61131-2
Input voltage range24 VDC -15% / +20%
Input current at 24 VDCTyp. 3.75 mA
Input circuitSource
Connection type3-wire connections
Input resistanceTyp. 6.4 kΩ
Channel-to-bus insulation voltage500 Veff
Sensor-supply powerMax. 12 W
Sensor-supply voltageModule power supply minus the short-circuit-protection voltage drop
Voltage drop at 500 mAMax. 2 VDC
Sensor-supply summation current0.5 A
ENVIRONMENT, APPROVALS & INTEGRATION
Sensor-supply short-circuit protectionYes
Electrical isolationChannels isolated from bus; channels not isolated from each other
Horizontal mountingSupported
Vertical mountingSupported
Installation elevationNo limitation from 0 to 2000 m
Above 2000 mReduce ambient limit by 0.5°C per 100 m
Degree of protectionIP20 per EN 60529
Horizontal operating temperature-25 to 60°C
Vertical operating temperature-25 to 50°C
Storage temperature-40 to 85°C
Transport temperature-40 to 85°C
Relative humidity5 to 95%, non-condensing
Module pitch12.5 +0.2 mm
CEYes
UKCAYes
ULcULus E115267
Hazardous-location approvalcCSAus 244665; Class I, Division 2, Groups ABCD, T5
ATEXZone 2, II 3G Ex nA nC IIA T5 Gc
Marine approvalsDNV, CCS, LR, KR, ABS and BV
KCYes