BACKPLANE, INTERFACES & POWER
Module functionX20 Compact-S PLC base
Backplane supportCompact-S PLC and power supply module
Serial interface1 × RS232
CAN interface1 × CAN bus
CAN terminationIntegrated terminating resistor
B&R ID code0xEB09
Bus power consumption0.55 W
I/O supply voltage24 VDC
Permissible contact load10 A
Electrical isolationBus, CAN and RS232 are not isolated from each other
Horizontal mountingYes — horizontal orientation
Vertical mountingYes — vertical orientation
MOUNTING, ENVIRONMENT & APPROVALS
Installation elevation0 to 2000 m without limitation
High-altitude deratingReduce ambient limit 0.5°C per 100 m above 2000 m
Degree of protectionIP20 per EN 60529
Operating temperature-25 to 60°C horizontal; -25 to 50°C vertical
Storage / transport temperature-40 to 85°C
Internal I/O powerNot applicable
Relative humidity5 to 95%, non-condensing
Pitch37.5 +0.2 mm
Included partsLeft and right X20 end cover plates
ConformityCE and UKCA
UL approvalcULus E115267
Marine approvalsDNV, CCS, LR, KR, ABS and BV