01
OFFICIAL POWER-SUPPLY DATA
X2X feed, I/O power & protection
B&R supply data arranged for current budgeting, protected outputs, redundancy, isolation and environmental installation.
Module functionX2X Link and internal I/O supply feedI/O polarity protectionNot provided
B&R ID code0x1BC0I/O nominal output24 VDC field supply
Status indicatorsOverload, operating state and module statusPermissible contact load10 A
Internal I/O consumption0.6 WSupply isolationX2X feed isolated; I/O feed not isolated
X2X supply consumption1.42 WMounting orientationHorizontal or vertical
X2X input voltage24 VDC -15% / +20% at X2X feedOperating temperature-25 to 60°C horizontal; -25 to 50°C vertical
X2X maximum input current0.7 AStorage and transport-40 to 85°C
X2X input fuseIntegrated and non-replaceableRelative humidity5 to 95%, non-condensing
X2X polarity protectionReverse-polarity protectedInstallation elevation0 to 2000 m without limitation
X2X nominal output power7 WHigh-altitude deratingReduce ambient limit by 0.5°C per 100 m
Parallel supply operationSupported for load sharingDegree of protectionIP20 per EN 60529
Redundant supply operationSupported with multiple supply modulesRequired power bus baseX20BM01 or node-switch version X20BM05
X2X overload behaviorShort-circuit proof with temporary overloadRequired terminal blockX20TB12, ordered separately
I/O feed input24 VDC -15% / +20% at field-power pathModule pitch12.5 +0.2 mm
Required I/O line fuseMaximum 10 A slow-blowCertification scopeCE, UKCA, UL, HazLoc and marine approvals listed