Description:TRICONEX 9662-610: Digital input/output termination panels; 16 channels; Modbus TCP/IP; IP67; hot-swappable.
Product condition: New
Packing condition:Factory Packing
100% insured shipping: A guarantee for your purchases
PLC Autocontroller DELIVER PARTS TO WORLD.


![]()

| Manufacturer | TRICONEX |
| Item number | 9662-610 |
| Country of Origin | United States |
| Lead Time | In stock |
| After-Sales Support | 12-months |
| HS Code / Commodity code | 8537101190 |
Quotes are valid for 30 days from the day the quote is received unless stated otherwise at the time of quotation.
Yes,we offer one year warranty for all new products.
Yes. We worked with FEDEX/DHL/TNT/UPS/ allowing us to provide swift global delivery of parts to any corner of the world.
Normally 3-5 working days,some remote areas 5-7 days more.
PLC Autocontroller – 20 years of experience in automation supply, based in Xiamen, China.
Worldwide shipping via DHL/FedEx/TNT/UPS
For more details or quotation inquiries, please contact:
Email: ab@mooreplc.com
Phone: +86-18106909650 (WhatsApp)
Wechat ID: dcsfcs
Sales Manager: May
Quick-glance specifications
|
Model |
9662-610 DO Termination Panel |
|
Architecture |
Triple Modular Redundant (TMR) |
|
Safety rating |
SIL 3 per IEC 61508 |
|
Channels |
16 DO, source or sink selectable |
|
Output voltage |
24 VDC ±10 % |
|
Max continuous current |
2 A per channel, 16 A total |
|
Response time |
< 2 ms typical |
|
Isolation |
1 500 Vrms field-to-logic, 250 V channel-to-channel |
|
Protection |
short-circuit, over-temp, overload & self-healing |
|
Diagnostics |
command/read-back mismatch, V/I monitoring per channel |
|
Hot-swap |
yes, rack remains powered |
|
Operating temp |
–40 °C to +85 °C |
|
Enclosure rating |
IP67 with cover closed |
|
Dimensions / weight |
100 × 50 × 20 mm, 250 g |
|
Mounting |
35 mm DIN-rail or panel |
Typical plant fit
ESD systems: solenoid valves, relays, beacons.
Compressor / pump skids: unload valves, motor contactors.
Fire & gas: deluge valves, fire-damper actuators, foam pumps.
Why engineers like it
Triple-output driver chips—one fails, the board keeps the load energised.
Replaceable 5 × 20 mm 2 A fuses; swap in seconds without touching wires.
Built-in freewheeling diodes—drive inductive loads directly, no external suppressor.
Top-mounted bi-colour LED: green = commanded ON, red = read-back fault.