Products
Based on over 5000 reviews
Description:TRICONEX 8110: Trident high-density I/O rack; supports redundant power and communications; used to expand I/O capacity.
Product condition: New
Packing condition:Factory Packing
100% insured shipping: A guarantee for your purchases
PLC Autocontroller DELIVER PARTS TO WORLD.


![]()

| Manufacturer | TRICONEX |
| Item number | 8110 |
| Country of Origin | United States |
| Lead Time | In stock |
| After-Sales Support | 12-months |
| HS Code / Commodity code | 8537101190 |
Quotes are valid for 30 days from the day the quote is received unless stated otherwise at the time of quotation.
Yes,we offer one year warranty for all new products.
Yes. We worked with FEDEX/DHL/TNT/UPS/ allowing us to provide swift global delivery of parts to any corner of the world.
Normally 3-5 working days,some remote areas 5-7 days more.
1.What it is
The 8110 is the physical heart of every TRICONEX Tricon Safety Instrumented System (SIS).
Built for SIL-3, TMR (Triple Modular Redundancy) architecture, it gives you three independent legs of power, data and diagnostics in a single 19-inch rack—no single point of failure, no hot-spare gaps.
2.Key technical data
|
Mechanical / Power |
Specification |
|
Rack slots |
32 high-density I/O slots (4 rows × 8) |
|
Foot-print |
482 mm W × 222 mm H × 333 mm D (19" × 5U) |
|
Weight (empty) |
24.5 kg |
|
Input power |
10 A @ 120 VDC (redundant supplies) |
|
Isolation |
1 500 V RMS module-to-bus |
|
Temp / Humidity |
40 °C … +70 °C / 5 … 95 % RH non-condensing |
|
Shock / Vibe |
5 g ½-sine 20 ms / 0.03 g 5-500 Hz |
|
Enclosure rating |
IP 20 (chassis); conformal-coated back-plane |
|
Certifications |
SIL 3 per IEC 61508, ATEX, CE, UL, cUL |
|
Communication on back-plane |
Ports |
|
TriBus (internal TMR) |
3 × parallel leg buses |
|
I/O expansion |
6 × RS-485 (isolated, 115 kbps) |
|
Remote chassis link |
2 × fibre or RS-485 per project |
|
Time sync |
1 PPS or IRIG-B optional |
Where it is used
Oil & gas ESD, LNG trains, refinery fire & gas, chemical reactor interlocks, nuclear auxiliary systems, power-gen turbine protection—any place where IEC 61511 demands a SIL-3 response time < 100 ms.
Why 8110 still matters
• Hot-swappable I/O – replace any module without tripping the process.
• Triple power buses – keep two on-line while you service the third.
• Field-proven for > 30 years; spares and upgrade CPUs remain available worldwide.
Need a quote or compatibility check?
E-mail: ab@mooreplc.com | WeChat / WhatsApp: +86-18106909650
What happens next?
Leave A Message
Scan to Wechat :